User manual SILENT KNIGHT SD505-DTS INSTALLATION
DON'T FORGET : ALWAYS READ THE USER GUIDE BEFORE BUYING !!!
If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Diplodocs provides you a fast and easy access to the user manual SILENT KNIGHT SD505-DTS. We hope that this SILENT KNIGHT SD505-DTS user guide will be useful to you.
Manual abstract: user guide SILENT KNIGHT SD505-DTSINSTALLATION
Detailed instructions for use are in the User's Guide.
[. . . ] SD505-ADHR Duct Detector Housing With Relay Module & SD505-DTS Installation Instructions
The following are instructions on how to install the SD505-ADHR & SD505-DTS to a Silent Knight Addressable control panel.
Mounting Instructions
Follow these steps to mount the SD505-ADHR: 1. Remove paper backing from mounting template (packaged in installation kit) and affix to duct at installation location. [. . . ] The intake sampling tube is a piece of steel piping with a series of holes drilled the entire length of the tube. The tube should be cut to a size that allows it to extend the entire width of the duct. The exhaust tube is a piece of steel piping measuring 7 inches.
P/N 151126
50 32° to 120° F (0° to 49° C) 10-85% RH SD505-APS SD505-AIS 500-4000 fpm 300-4000 fpm 0. 85 to 1. 15% 0. 5 to 0. 81% per foot per foot
SD505-ADHR Duct Detector Housing With Relay Module & SD505-DTS Installation Instructions
The pressure differential between the input sampling tube and exhaust tube should be greater than 0. 01" and less than 1. 2" of water.
Wiring Instructions
This section contains information on how to connect the SD505-ADHR to a power source, to a fan motor, and to a SD505-DTS remote test station. Wiring must conform to applicable local codes, ordinances, and regulations covering this type of device. Refer to NFPA 90A and NFPA 72E for additional information on duct smoke detector operation and installation.
Figure 1: Sampling Tube Orientation
5. Firmly insert the provided stopper into the end of the intake sampling tube.
Standard Lengths for Intake Sampling Tubes STS-2. 5 STS-5. 0 STS-10. 0 For duct widths of 1. 0' to 2. 5' For duct widths of 2. 5' to 5. 0' For duct widths of 5. 0' to 10. 0'
7. Mount the detector by placing the detector/sampling tube assembly into position and secure to duct housing using mounting screws. Verify that air velocity is appropriate for the type of smoke detector you are using by checking specifications of installation and, if necessary, by using air velocity meter (Alnor Model 6, 000P or equivalent). Verify proper air sampling by using a differential pressure gauge (Dwyer Model 4000 or equivalent). See Figure 2 for connections.
Figure 3: Wire Routing Example
Important! [. . . ] The SD505-DTS also provides visual access to the SD505-ADHR in installations where the SD505-ADHR cannot physically be seen.
SD505-DTS Wiring
Wire the SD505-DTS to the SD505-ADHR as shown in Figure 8.
Figure 9: SD505-DTS Mounting and Assembly
SD505-DTS Specifications
Parameter Current Draw Standby:
Supervised Power Limited
Rating 6 mA 6 mA
Alarm:
Dimensions (including red 4-3/4" H x 3" W x 1-3/4" D trim plate): 12. 07 cm x 7. 62 cm x 4. 45 cm Operating Temperature: Operating Voltage: 32° F to 120° F (0° C to 49° C) 10 VDC
Figure 8: SD505-DTS Wiring Connections
Mounting The SD505-DTS
The SD505-DTS mounts into a single gang electrical switch box. See Figure 9.
7550 Meridian Circle Maple Grove, MN 55369-4927 763-493-6455 or 800-328-0103 Fax: 763-493-6475 www. silentknight. com
4
© 2006 Silent Knight PN 151126 Rev C [. . . ]